Ventable, fixed-orifice, bypass/restrictive, priority flow control valve with integral T-8A control cavity

Capacity: 6 gpm23 L/min. | Cavity: T-21A
FVCA8 : Ventable, fixed-orifice, bypass/restrictive, priority flow control valve with integral T-8A control cavity
Technical Features [ + ]

This valve is a ventable, bypass/restrictive, fixed-orifice, priority flow control with an integral pilot control cavity. The pilot control cavity will accept any T-8A pilot pressure or directional control cartridge. It takes an input flow at port 1 and uses it to satisfy the priority flow at port 3. If the input flow exceeds the priority flow requirement, the excess flow is bypassed out of port 2. Bypass flow may be used for a secondary circuit. Depending on which pilot control valve is installed in the T-8A cavity, priority flow can be selected electrically, manually, hydraulically or pneumatically.

  • Customer must specify a flow rating. Factory set flow ratings are within +/- 10% of the requested setting.
  • Using a pressure control in the T-8A pilot control cavity will limit the pressure at the priority port (port 3). If pressure on the bypass port (port 2) exceeds the setting of the pressure control, priority flow will be shut off and all the flow will go out the bypass port.
  • Maximum pressure at port 3 should be limited to 3000 psi (210 bar).
  • NOTE: With the -8 control option, the main stage valve should first be installed to the correct torque value. The T-8A pilot control valve should then be installed into the main stage valve to its required torque value.
  • Both priority and bypass flow are usable up to the system operating pressure.
  • Priority remains relatively constant regardless of variation in input flow.
  • Bypass flow is not available until priority flow requirements are satisfied, except when the valve is vented. When port 4 (vent) is open, all flow diverts to port 2 if pressure at port 1 (inlet) is 150 psi (10,5 bar) or higher.
  • Pressure at the bypass port (port 2) may exceed pressure at the priority port (port 3).
  • The sharp-edged orifice design minimizes flow variations due to viscosity changes.
  • The -8 control option allows the pilot control valve to be incorporated directly into the end of the cartridge via the T-8A cavity. These pilot control cartridges are sold separately and include electro-proportional, solenoid, air pilot, and hydraulic pilot operation. See Pilot Control Cartridges.
  • Incorporates the Sun floating style construction to minimize the possibility of internal parts binding due to excessive installation torque and/or cavity/cartridge machining variations.
Technical Data [ + ]
Note: Data may vary by configuration. See CONFIGURATION section.
Cavity T-21A
Series 1
Capacity 6 gpm23 L/min.
Maximum Operating Pressure 5000 psi350 bar
Nominal Vent Flow 46 in³/min.0,75 L/min.
Maximum Input Flow 15 gpm60 L/min.
Pilot Control Cavity T-8AT-8A
Pilot Control Valve Installation Torque 20 - 25 lbf ft27 - 33 Nm
Pilot Control Valve Hex Size 7/8 in.22,2 mm
Valve Hex Size 7/8 in.22,2 mm
Valve Installation Torque 30 - 35 lbf ft41 - 47 Nm
Model Weight .30 lb0,15 kg
Seal kit - Cartridge Buna: 990021007
Seal kit - Cartridge Polyurethane: 990021002
Seal kit - Cartridge Viton: 990021006
Performance Curves [ + ]
FAQs [ + ]

There are exactly 250 Sun drops in a cubic inch or 15 in a cc.

In a meter-in flow control circuit if the pump is set at 3000 psi and the load is 2000 psi the drop through the flow control is 1000 psi. In a meter-out circuit with the load at 2000 psi the drop through the flow control is 2000 psi.

We claim +/- 10%. We set to +/- 5% in production testing to allow for differences in customers' conditions. If you want accuracy, stay in the bottom 2/3rds of the range. Our 12 gpm (45 L/min.) flow controls are quite flat at 9 gpm (34 L/min.) and dead flat below 6 gpm (23 L/min.), until you get to the bottom of the range. Below about .25 gpm (1 L/min.), spool leakage and orifice conditions start to limit accuracy.

I am afraid not. Unless you are overflowing your current valve and correctly size ours, you are not likely to notice any improvement. Priority flow controls are not efficient devices. They are an easy way to get more than 1 source of oil from 1 pump but they can generate a lot of heat. Try to size your actuators so the pressures are similar on both the priority and the bypass circuits. If you can't do that, try to have the lower flow leg be the lower pressure. The pump pressure is determined by whichever leg is higher and if there is flow that is taking a pressure drop that is not doing work it is creating heat.

All flow is blocked, hence the term priority. The priority flow has to be satisfied.

The valve acts as a 2 port restrictive flow control.

The spring force in our flow controls equates to about 100 psi (7 bar). This is high enough to give the valves acceptable capacity and not too high for proper circuit operation. 100 psi (7 bar) is the spring force; at the upper end of the flow control's range, the drop through the valve will be as high as 250 psi (17 bar) before it starts modulating.

Only external seals are serviceable.  Sun offers replacement seal kits for all cartridge models. The applicable kit part number can be found in the product page's Technical Data table or by using our Cartridge Seal Kit search function located under Accessories. Please note: Converting the external seals from one material to another does not ensure fluid compatibility with that material due to the existence of internal seals within the cartridge.
Notes [ + ]
  • Compound cartridge (pilot and main stage) assembly information is provided for reference only. Cartridges must be ordered separately and assembled at point of use.
Additional Resources [ + ]